OSHA 29 CFR 1910.106 (e)(2)(ii)(b): Incidental storage or use of flammable and combustible liquids. (b) The quantity of liquid that may be located outside of an inside storage room or storage cabinet in a building or in any one fire area of a building shall not exceed: (1) 25 gallons of Class IA liquids in containers (2) 120 gallons of Class IB, IC, II, or III liquids in containers (3) 660 gallons of Class IB, IC, II, or III liquids in a single portable tank. | EAGLE Safety Cabinets 


Click on product images for detailed product information |
OSHA 29 CFR 1910.106 (d)(3)(i&ii): Design, construction, and capacity of storage cabinets -(I) Maximum capacity. Not more than 60 gallons of Class I or Class II liquids, nor more than 120 gallons of Class III liquids may be stored in a storage cabinet. (ii) Fire resistance. Storage cabinets shall be designed and constructed to limit the internal temperature to not more than 325°F when subjected to a 10-minute fire test using the standard time-temperature curve as set forth in Standard Methods of Fire Tests of Building Construction and Materials, NFPA 251-1969. All joints and seams shall remain tight and the door shall remain securely closed during the fire test. Cabinets shall be labeled in conspicuous lettering, FLAMMABLE-KEEP FIRE AWAY. (a) Metal cabinets constructed in the following manner shall be deemed to be in compliance. The bottom, top, door, and sides of cabinet shall be at least No. 18 gauge sheet iron and double walled with 1½-inch air space. Joints shall be riveted, welded, or made tight by some equally effective means. The door shall be provided with a three-point lock, and a door sill shall be raised at least 2 inches above the bottom of the cabinet. |