Safety, Storage & Security Cabinet Regulations
Key excerpts of pertinent Codes and Regulations
OSHA 29 CFR 1910.106(e)(2)(ii)(b): www.osha.gov
Incidental storage or use of flammable and combustible liquids.
(b) The quantity of liquid that may be located outside of an inside
storage room or storage cabinet in a building or in any one fire area
of a building shall not exceed: (1) 25 gallons of Class IA liquids in
containers (2) 120 gallons of Class IB, IC, II or III liquids in containers
(3) 660 gallons of Class IB, IC, II or III liquids in a single portable
tank
OSHA 29 CFR 1910.106(d)(3)(i&ii): www.osha.gov
Design, construction, and capacity of storage cabinets - (i)
Maximum capacity. Not more than 60 gallons of Class l or Class
ll liquids, nor more than 120 gallons of Class lll liquids may be stored
in a storage cabinet.
(ii) Fire resistance. Storage cabinets shall be designed
and constructed to limit the internal temperature to not more than 325ºF.
when subjected to a 10-minute fire test using the standard time-temperature
curve as set forth in Standard Methods of Fire Tests of Building Construction
and Materials, NFPA 251-1969. All joints and seams shall remain tight
and the door shall remain securely closed during the fire test. Cabinets
shall be labeled in conspicuous lettering, "Flammable-Keep Fire Away."
(a) Metal cabinets constructed in the following manner shall be deemed
to be in compliance. The bottom, top, door, and sides of cabinet shall
be at least No. 18 gauge sheet iron and double walled with 11/2" air
space. Joints shall be riveted, welded or made tight by some equally
effective means. The door shall be provided with a three-point lock,
and the door sill shall be raised at least 2" above the bottom of the
cabinet.
Uniform Fire Code 79.201**: www.ufca.net
(g) Storage Cabinets.
1. General. When provisions of this code require that
liquid containers be stored in storage cabinets, such cabinets and storage
shall be in accordance with this section. Cabinets shall be conspicuously
labeled in red letters on contrasting background FLAMMABLE - KEEP FIRE
AWAY.
2. Quantities. The quantity of Class I or Class II
liquids shall not exceed 60 gallons and the total quantities of all
liquids in a storage cabinet shall not exceed 120 gallons.
3. Construction. Cabinets may be constructed of wood
or metal. Cabinets shall be listed or constructed in accordance with
the following:
A. Unlisted metal cabinets. Metal cabinets shall be
of steel having a thickness of not less than 0.043". The cabinet, including
the door, shall be double walled with 11/2" airspace between the walls.
Joints shall be riveted or welded and shall be tight fitting. Doors
shall be well fitted, self-closing and equipped with a latching device.
The bottom of the cabinet shall be liquid-tight to a height of at least
2".
NFPA Code 30 - 2003 Edition*: www.nfpa.org
6.3.4 The storage cabinet shall not be required by
this code to be vented for fire protection purposes, and vent openings
shall be sealed with the bungs supplied with the cabinet or with bungs
specified by the cabinet manufacturer. However, if the storage cabinet
is vented for any reason, the cabinet shall be vented directly to outdoors
in such a manner that will not compromise the specified performance
of the cabinet and in a manner that is acceptable to the authority having
jurisdiction.
NFPA 58 LP Gas Code - 2004 Edition*: www.nfpa.org
8.4.2 Protection of Cylinders. 8.4.2.1 Cylinders at
a location open to the public shall be protected by either of the following:
(1) An enclosure in accordance with 6.16.5.2(a): Requires a fence enclosure
for areas where cylinders are loaded, unloaded, etc. or
(2) A lockable ventilated metal locker or rack that prevents tampering
with valves and pilferage of the cylinder.
6.4.1 Location of Storage Outside of Buildings
6.4.1.1 Storage outside of buildings for cylinders
awaiting use, resale, or part of a cylinder exchange point shall be
located as follows:
(1) At least 5 ft (1.5m) from any doorway or opening
in a building frequented by the public where occupants have at least
two means of egress as defined by NFPA 101, Life Safety Code.
(2) At least 10 ft (3m) from any doorway or opening
ina building or sections of a building that has only one means of egress
(3) At least 20ft (6.1m) from any automotive service
station fuel dispenser
OSHA 29 CFR1910.110 Liquid Petroleum Gas: www.osha.gov
Storage within buildings not frequented by the public (such
as industrial buildings.) The quantity of LP-gas stored shall
not exceed 300 pounds (approximately 2,550 cubic feet in vapor form)
OSHA 29 CFR1910.253(b)(2) Storage of Cylinders - General
www.osha.gov
(b)(2)(ii) Inside of buildings, cylinders shall be
stored in a well-protected, well-ventilated, dry location, at least
20 (6.1m) feet from highly combustible materials such as oil or excelsior.
Cylinders should be stored in definitely assigned places away from elevators,
stairs, or gangways. Assigned storage spaces shall be located where
cylinders will not be knocked over or damaged by passing or falling
objects, or subject to tampering by unauthorized persons. Cylinders
shall not be kept in unventilated enclosures such as lockers and cupboards.
(b)(3)(i) For storage in excess of 2,000 cubic feet
(56m(3)) total gas capacity of cylinders or 300 pounds (135.9 kg) of
liquefied petroleum gas, a separate room or compartment conforming to
the requirements specified in paragraphs (f)(6)(i)(H) and (f)(6)(i)(I)
of this section shall be provided, or cylinders shall be kept outside
or in a special building. Special buildings, rooms or compartments shall
have no open flame for heating or lighting and shall be well ventilated.
They may also be used for storage of calcium carbide in quantities not
to exceed 600 (271.8 kg) pounds, when contained in metal containers
complying with paragraphs (g)(1)(i) and (g)(1)(ii) of this section.
CSA International B149.2 5.1.7: www.csa-international.org
The relief valve shall have direct communication at all times with the
vapour space of the cylinder.
CSA International B149.2 5.5.2.1(c):
The storage cabinet: (iii)wall or top cover material
shall be either metal wire of not less than No.9 SWG (3.7 mm), having
openings not greater than 2 x 2 in (50 x 50 mm), or sheet metal; (iv)
shall be ventilated to the outside air on a minimum of two sides at
the top and bottom of the cabinet walls; and (v) shall be securely anchored
in an upright position.
NFPA Code 30 - 2003 Edition: www.nfpa.org
3.3.18 Hazardous Material or Hazardous Chemical. Material
presenting dangers beyond the fire problems relating to flash point
and boiling point.
3.3.19 Hazardous Materials Storage Locker. A movable
prefabricated structure, manufactured primarily at a site other than
the final location of the structure and transported completely assembled
or in a ready-toassemble package to the final location. It is intended
to meet local, state, and federal requirements for outside storage of
hazardous materials.
Section 6.6* Hazardous Materials Storage Lockers. 6.6.2
Subsections 6.6.3 and 6.6.4 shall apply to storage of flammable and
combustible liquids in containers, in hazardous material storage lockers
(hereinafter referred to as lockers) that are located outside.
6.6.3 The design and construction of a locker shall
meet all applicable local, state, and federal regulations and requirements
and shall be subject to the approval of the authority having jurisdiction.
Movable, prefabricated structures that have been examined, listed, or
labeled by an organization acceptable to the authority having jurisdiction
for use as a hazardous materials storage facility shall be acceptable.
6.6.3.1 Lockers governed by this standard shall not
exceed 1500 ft2 (140 m2) gross floor area. Vertical stacking of lockers
shall not be permitted.
6.6.3.2 Where electrical wiring and equipment is required,
it shall comply with 6.4.2.6.
6.6.3.3 Where dispensing or filling is permitted inside
a locker, operations shall comply with the provisions in Chapter 7.
6. 6.3.4 Ventilation shall be provided in accordance
with 6.4.2.7.
6.6.3.5 Lockers shall include a spill containment system
to prevent the flow of liquids from the structure under emergency conditions.
The containment system shall have sufficient capacity to contain 10
percent of the volume of containers allowed or the volume of the largest
container, whichever is greater.
6.6.4 Designated sites shall be provided for the location
and use of lockers and shall be subject to the approval of the authority
having jurisdiction. The designated sites shall be arranged to provide
at least the minimum separation distance between individual lockers,
distance from locker to property line that is or can be built upon,
and distance from locker to nearest side of public ways or to important
buildings on the same property, as given in Table 6.6.4 and explanatory
notes 1, 2, 3, 4,as applicable.
| Table 6.6.4 Designated
Sites (1) |
Area of Designated Site (2)(ft) |
Distance Between Individual Lockers
(ft) |
Distance From Locker to Property
Line That is or Can be Built Upon (3)(ft) |
Distance From Locker to Nearest
Side of Public Ways or To Important Buildings on Same Property(3,4) |
greater/less than 100 |
5 |
10 |
5 |
greater than 100 less than 500 |
5 |
20 |
10 |
greater than 500 less than 1500 (5) |
5 |
30 |
20 |
For SI units, 1 ft = 0.3 m; 1 ft 2 = 0.09 m 2. ( 1 )
If the locker is provided with a fire resistance rating of not less
than 4 hours and deflagration venting is not required in accordance
with 6.4.2.4, all distances required by Table 6.6.4 shall be permitted
to be waived. ( 2 ) Site area limits are intended to differentiate the
relative size and thus the number of lockers that are permitted in one
designated site. ( 3 ) Distances applies to properties that have protection
for exposures, as defined. If there are exposures and such protection
does not exist, the distances shall be doubled. ( 4 ) When the exposed
building has an exterior wall, facing the designated site, that has
a fire-resistance rating of at least 2 hrs. and has no openings to above-grade
areas within 10 ft (3 m) horizontally and no openings to below-grade
areas within 50 ft (15 m) horizontally of the designated area, the distances
can be reduced to half of those shown in the table, except they shall
never be less than 5 ft (1.5 m). ( 5 ) When a single locker has a gross
single story floor area that will require a site area limit of greater
than 1500 ft 2 (139 m2) or when multiple units exceed the area limit
of 1500 ft 2. (140 m2), the authority having jurisdiction shall be consulted
for approval of distances.
6.6.4.1 Once the designated site is approved, it shall
not be changed without the approval of the authority having jurisdiction.
6.6.4.2 More than one locker shall be permitted on
a designated site, provided that separation distance between individual
lockers is maintained in accordance with Table 6.6.4.
6.6.4.3 Where the approved designated storage site
is accesible to the general public, it shall be protected from tampering
or trespassing. 6.6.4.4 Storage Practices.
6.6.4.4.1 Containers of liquid in their original shipping
packages shall be permitted to be stored either palletized or solid
piled. Unpackaged containers shall be permitted to be stored on shelves
or directly on the floor of the locker. Containers over 30 gal. (114
L) capacity storing Class I or Class II liquids shall not be stored
more than two containers high. In all cases, the storage arrangement
shall provide unrestricted access to and egress from the locker.
6.6.4.4.2 No other flammable or combustible materials
storage shall be permitted within the designated site approved for lockers.
6.6.4.4.3 Placarding or warning signs for lockers shall be in accordance
with applicable local, state, and federal regulations or with NFPA 704,
Standard System for the Identification of the Hazards of Materials for
Emergency Response.
HAZARD COMMUNICATION STANDARD OSHA 29 CFR 1910.1200(g)(8):
The employer shall maintain in the workplace copies of the required
material safety data sheets for each hazardous chemical, and shall ensure
that they are readily accessible during each work shift to employees
when they are in their work area(s). (Electronic access, microfiche,
and other alternatives to maintaining paper copies of the material safety
data sheets are permitted as long as no barriers to immediate employee
access in each workplace are created by such options)
*Reprinted with permission from NFPA 30 Flammable and
Combustible Liquids Code 2003 Edition. Copyright ©2003, National Fire
Protection Association, Quincy, MA 02269. This reprinted material is
not the complete and official position of the National Fire Protection
Association, on the referenced subject which is represented only by
the standard in its entirety.
*Reprinted with permission from NFPA 58 LP Gas Code 2004 Edition. Copyright
©2004, National Fire Protection Association, Quincy, MA 02269. This
reprinted material is not the complete and official position of the
National Fire Protection Association, on the referenced subject which
is represented only by the standard in its entirety.
**Portions of this work are reproduced from the 1997 edition of the
Uniform Fire Code™, copyright©1997, with the permission of the publisher,
the International Conference of Building Officials (ICBO). ICBO assumes
no responsibility for the accuracy or the completion of summaries provided
therein.
Related Information
A Guide
To Justrite® Safety Cabinets
A
Guide To Justrite® Safety Cans